Publication

Peak cooling load shift capability of a thermal energy storage system integrated with an active insulation system in US clima...

Publication Type
Journal
Journal Name
Energy and Buildings
Publication Date
Page Number
122484
Volume
277
Issue
0

This study aims to evaluate a thermal energy storage (TES) system integrated with an active insulation system (AIS) to form a TES + AIS integrated wall system as a partition and as a secondary cooling system to shift the peak load and reduce cooling energy consumption. To understand and demonstrate its cooling performance, the TES + AIS integrated wall system was installed in an office building in Oak Ridge, Tennessee. To investigate the effect of the TES + AIS integrated wall system in a typical office building and various climate zones, the US Department of Energy’s prototype office building model was modified to accommodate the proposed system. Results showed that the minimum size of the proposed system to achieve energy savings varies depending on climate conditions. The minimum size of the proposed system for cooling energy saving and shifting peak cooling demand in climate zones 2, 3, and 5 is 29.7 m2, whereas it is 44.6 m2 in zones 4 and 6. By installing the minimum size of the proposed system, 11.3 % to 16.4 % of cooling energy can be shifted during discharge hours in a representative summer day.