Skip to main content
SHARE
Publication

Peak load reduction and load shaping in HVAC and refrigeration systems in commercial buildings by using a novel lightweight d...

by Christopher J Winstead, Mahabir S Bhandari, James J Nutaro, Phani Teja V Kuruganti
Publication Type
Journal
Journal Name
Applied Energy
Publication Date
Page Number
115543
Volume
277
Issue
1

Reducing peak power demand in a building can reduce electricity expenses for the building owner and contribute to the efficiency and reliability of the electrical power grid. For the building owner, reduced expenses come from the reduction or elimination of peak power charges on electricity bills. For the power system operator, reducing peak power demand leads to a more predictable load profile and reduces stress on the electric grid system. We present a computationally inexpensive, dynamic, and retrofit-deployable control strategy to effect peak load reduction and load shaping. The effectiveness of the control strategy is examined in a simulation with 80 air-conditioning units and 40 refrigeration units. The results show that a peak demand reduction of 60 kW can be achieved relative to peak demand in a typical set point–based approach. The proposed strategy was deployed in a gymnasium building with four rooftop HVAC units, where it showed over 15% peak demand (kW) reduction savings while maintaining or lowering energy consumption (in kilowatt-hours) relative to the set point–based thermostat controls.