Datasets of Faults in Variable Air Volume Terminal Units in a Multi-Zone Commercial Building

by Sungkyun Jung, Yeobeom Yoon, Piljae Im
Publication Type
Journal
Journal Name
Scientific Data
Publication Date
Page Number
763
Volume
12

Faults in HVAC systems can decrease system efficiency and equipment lifespan, leading to 5%–30% of energy consumption being wasted in commercial buildings. We identified two common faults in HVAC variable air volume systems: a stuck damper fault in the variable air volume terminal unit and a discharge airflow sensor fault. We conducted three sets of damper stuck tests and two sets of airflow sensor tests, each including a fault-free scenario and scenarios with varying levels of faults, over one day. The faults were implemented in Oak Ridge National Laboratory’s two-story Flexible Research Platform building to generate a high-quality, well-controlled dataset covering fault-induced and fault-free scenarios. The test building, fault test scenarios, and data validation are described here. The open-source dataset includes 1 min intervals of weather and building data on the presence and absence of building faults. This dataset can be used to analyze the effects of HVAC system faults on system operation and indoor building conditions, and to develop or evaluate a fault detection and diagnosis algorithm.