August 2009

Conference Paper

Testing of 3-meter Prototype Fault Current Limiting Cables

By:
Gouge, Michael J; Duckworth, Robert C; Demko, Jonathan A; Rey, Christopher M; Thompson, James R; Lindsay, David T; Tolbert, Jerry C; Willen, Dag; Lentge, Heidi; Thidemann, Carsten; Carter, Bill
Journal Name:
IEEE Transactions on Applied Superconductivity
Page Number:
1744-1747
Volume:
19
Issue Number:
3
Publication Date:
August 2009
Conference Name:
2008 Applied Superconductivity Conference
Conference Location:
Chicago, Illinois, United States of America
View DOI Listing:
https://doi.org/10.1109/TASC.2009.2018310

Abstract

Two 3-m long, single-phase cables have been fabricated by Ultera from second generation (2G) superconductor supplied by American Superconductor. The first cable was made with two layers of 2G tape conductor and had a critical current of 5,750 A while the second cable had four layers and a critical current of 8,500 A. AC loss was measured for both cables at ac currents of up to 4 kArms. Ultera performed initial fault current studies of both cables in Denmark with limited currents in the range from 9.1 to 44 kA. Results from these tests will provide a basis for a 25-m long, three-phase, prototype cable to be tested at ORNL early next year and a 300-m long, fault current limiting, superconducting cable to be installed in a ConEd substation in New York City.