- By:
- Kueck, John D; Kirby, Brendan ; Laughner, T; Morris, K
- Publication Date:
- July 2009
- Conference Name:
- IEEE Power Engineering Society General Meeting
- Conference Location:
- Calgary, Canada
- Conference Sponsor:
- IEEE
Abstract
As power system costs rise and capacity is strained demand response can provide a significant system reliability benefit at a potentially attractive cost. The 162 room Music Road Hotel in Pigeon Forge Tennessee agreed to host a spinning reserve test. The Tennessee Valley Authority (TVA) supplied real-time metering and monitoring expertise to record total hotel load during both normal operations and testing. Preliminary testing showed that hotel load can be curtailed by 22% to 37% depending on the outdoor temperature and the time of day. The load drop was very rapid, essentially as fast as the 2 second metering could detect.