December 2008

ORNL Report

Air Curtain Stability and Effectiveness in Open Vertical Refrigerated Display Cases: Project Final Report

By:
Walker, David; Faramarzi, Ramin; Navaz, Homayun; Dabiri, Dana
Publication Date:
December 2008

Abstract

The purpose of this research project was to find the optimum geometric configurations and flow parameters that can minimize the infiltration rate through the air curtain of an open vertical refrigerated display case (OVRDC). Air curtains in OVRDCs function as an invisible barrier between the cold air inside and the warm air outside the case. This project developed a comprehensive and systematic approach to minimize the entrainment and infiltration of warm air into the OVRDC. It provided a global solution to optimize the performance of an air curtain through adjusting pertinent flow parameters and case geometry. As part of the project, a modular display case simulator, referred to as the proof-of-concept air curtain (POCAC), was manufactured for the parametric studies. In this modular display case, the key geometry and flow parameters were varied, and the infiltration rate was measured. As part of the project, thermal and tracer gas analysis of the baseline and prototype display cases were also performed in a controlled environment. A matrix based on all possible design and operational permutations was constructed with the infiltration rate being the outcome of this matrix. This matrix was populated using results from actual experimental measurements and validated by computational fluid dynamics modeling. All problem variables were referred to as the input vector of all parameters that can be altered, and the output was the infiltration rate. An artificial neural network (ANN) program was used to provide the linkage between the input vector (problem variables) and the problem outcome (infiltration). This ANN program was trained based on actual infiltration data that was obtained by using a tracer gas. Furthermore, the technique was extended to measure the total flow rate of display cases. In this method, carbon dioxide as a tracer gas was introduced in the air flow stream and by measuring its concentration at the discharge air grille (DAG), return air grille, and the room the total flow rate and infiltration rate were determined. A base case was selected and a comparison of the predicted and measured infiltration rates validated the approach. The ANN was used to find those flow and geometrical parameters that can result into an improved and optimized display case with a reduced infiltration rate. Accordingly, the prototype was developed and tested. The comparison between the predicted reduced infiltration rate by the ANN for the prototype case and the measured quantities by the tracer gas and thermal analysis methods were consistent and encouraging. The results indicated that by just reducing the air velocity and throw angle at the DAG, a 7-8% reduction in the infiltration rate was achieved. As a result, the total case cooling load was decreased by roughly 7%, and both compressor power and daily energy usage decreased by 4%. The reduced infiltration rate allowed for system operating parameters to be altered, namely raising the suction pressure or the discharge air temperature, while maintaining product temperatures. This alteration resulted in additional compressor demand and daily energy savings of 9%, for a total of 13% savings. Further, based on the ANN and experimental results obtained by the POCAC, it was concluded that another 8-10% reduction in infiltration rate is possible by lowering the turbulence intensity at the DAG to 3% from the current value of 14%.