Advanced Wall Systems

ORNL Home ASTM Testing BEP Home Related Sites Work With Us Advanced Wall Systems Home

Hotbox Test R-value Database

Staqable Symmetry

 

Summary Of Hotbox Test Data And Calculations

 

Test 1

Test 2

Test 3

Tests performed Summer 2002 click here for test specifics

click here for test specifics

click here for test specifics

Total Hours

total length of time test wall was in chamber

411
387
355

C-TEMP

weighted average of surface and joint TC's,
climate side (°F)

26.6
27.3
25.6

M-TEMP

weighted average of surface and joint TC's,
meter side (°F)

67.6
75.8
75.8

C-JOINT

24.9
28.3
26.2

M-JOINT

63.4
75.2
74.3

MA-AIR-T

average of 36 air TC's, meter side (°F)

75.2
79.6
80.0

M-BAF-T

average of 24 baffle TC's, meter side (°F)

72.8
78.5
78.8

C-AIR-T

average of 48 air TC's, climate side (°F)

22.3
26.9
24.9

C-BAF-T

average of 36 baffle TC's, meter side (°F)

23.4
27.6
25.6

M-AIR-VC

air velocity, meter side (MPH)

0.40
0.46
0.45

C-AIR-VC

air velocity, climate side (MPH)

3.25
3.15
3.14

∆T

temperature difference across sample wall

41.0
48.5
50.2

T(mean)

mean temperature across sample wall

47.1
51.5
50.7

Qmb

energy exchange through meter box walls (Btu/hr)

-0.003
0.006
0.006

Qmb fl

meter box flanking loss, determined by calibrations

4.853
4.836
4.836

Qwall

calculated energy flow through specimen wall
(Qwall - Qsurr)

649.9
307.1
331.0

Face-To-Face Rwall

surface to surface R-value of wall (hr*ft2*°F/Btu)

4.0
10.1
9.7

Air-To-Air Ru wall

overall R-value of sample wall (air-to-air),
Rms air + Rwall + Rcs air (hr*ft2*°F/Btu)

5.2
11.0
10.7

Rms air

meter side air film resistance (hr*ft2*°F/Btu)

0.747
0.788
0.796

Rcs air

climate side air film resistance (hr*ft2*°F/Btu)

0.420
0.403
0.412